Communication manual 8400 protec PROFIBUS

Monitorings

Short interruption of PROFIBUS communication

65

L

EDS84DPBUS EN 2.0 - 09/2010

10.2

Short interruption of PROFIBUS communication

[10-1] Sequence for short-time interruption of communication

The master detects the communication fault and only after a few microseconds it transfers

the slave to the "WAIT_PRM" status of the DP state machine (see illustration

[10-1]

).

Only after the state chain of the DP state machine ending in the "DATA_EXCHANGE" status

(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the

slave (in milliseconds) continues to run.

Additional monitoring for the data exchange
For this reason an additional monitoring function for data exchange is available with

C13881

which is activated when "Data_Exchange" is exited and the parameterised time

(0 ... 65535 ms) has expired. The active monitoring triggers the response parameterised in

C13880

.

2133PFB006

POWER ON

WAIT_PRM

WAIT_CFG

DATA_EXCH

Slave_Diag
Get_Cfg

Set_Slave_Add

Slave_Diag

Chk_Cfg, not o.k.
Set_Prm, not o.k.

Chk_Cfg, o.k.

Slave_Diag
Set_Prm
Get_Cfg

Note!

The watchdog monitoring time does not continue to run when the slave does

not reach the "DATA_EXCHANGE" status due to repeated communication faults

(e.g. caused by loose contact).

Note!

Meet the following condition for the time setting:
Monitoring time for the data exchange (

C13881

)

Watchdog monitoring time

of the PROFIBUS (

C13882

).