Parameters relevant for the communication

C13882

C13885

C13886

Parameter | Name:

C13882 | Monitoring time: Watchdog

Data type: UNSIGNED_32

Index: 10693

d

= 29C5

h

Display of the watchdog monitoring time determined by the PROFIBUS master

• A change in the watchdog monitoring time is immediately effective.

• Monitoring starts with the receipt of the first telegram.

• When the value "0" is displayed, monitoring is deactivated.



Permanent interruption of PROFIBUS communication ( 64)

Display area

(min. value | unit | max. value)

0

ms

4294967295

Subcodes

Info

C13882/1

Monitoring time watchdog

C13882/2

DP-V1 MSC2

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13885 | Delete process data

Data type: UNSIGNED_8

Index: 10690

d

= 29C2

h

Selection of the process data which the controller is to continue to process in order to maintain the internal

communication in the event of a PROFIBUS failure.
Selection list

(Lenze setting printed in bold)

0 Use of the last master PDOs
1 PDOs are set to the value'0'

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13886 | Set ext. diagnostic bit by

Data type: BITFIELD_8

Index: 10689

d

= 29C1

h

Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to

be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).

• The diagnostic bit is sent from the controller to the host system where it is evaluated separately.

• The diagnostic bit is always set when a system error occurs.

• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.

• An extended diagnostic message is generally sent.
Value is bit-coded:

Info

Bit 0 Fault
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT