C13880 | reaction on communication failure, C13881 | monit. time: data exchange, C13880 – Lenze E84Dxxxx User Manual

Page 83: Is executed in the controller, For the "data_exchange" status, C13881, Is set, Lenze setting: "no response"), C13880/1, C13880/2

Advertising
background image

Communication manual 8400 protec PROFIBUS

Parameter reference

Parameters relevant for the communication

83

L

EDS84DPBUS EN 2.0 - 09/2010

C13880

C13881

Parameter | Name:

C13880 | Reaction on communication failure

Data type: UNSIGNED_8

Index: 10695

d

= 29C7

h

Monitoring response in case of a communication fault on the PROFIBUS

• A change of the monitoring response is effective immediately.



Permanent interruption of PROFIBUS communication ( 64)

Selection list

0 No response
1 Fault
3 Quick stop by trouble
4 Warning locked
6 Information

Subcodes

Lenze setting

Info

C13880/1

0: No response

The response set here for the "watchdog/data exchange"

monitoring is executed if the bus station ...

• does not receive a message from the master within

the watchdog monitoring time (during an active

connection displayed under

C13882/1

).

• detects that it is no longer in the "DATA_EXCHANGE"

status. Please see also the notes given under

C13881

.

C13880/2

0: No response

The response set here for "DPV1 MSC2" monitoring is

activated if, during the monitoring time (during an active

connection displayed in

C13882/2

), the node does not

receive a "DPV1 MSAC2" message from the master and

the MSAC2 connection is stopped from the slave.

Note:We recommend to set "Information" for the

response in order that no drive-relevant response takes

place.

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13881 | Monit. time: Data exchange

Data type: UNSIGNED_16

Index: 10694

d

= 29C6

h

If the DATA_EXCHANGE state has been exited, the response parameterised with

C13880/1

is carried out when the

time set here for the data exchange has expired.

• The value "65535" in this code deactivates monitoring.

• A change in monitoring is effective immediately.

• The value set here for the monitoring time must be smaller than the watchdog monitoring time (displayed under

C13882/1

).



Permanent interruption of PROFIBUS communication ( 64)

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 65535 ms

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT