C13852 | all words to standard device, C13853 | all words from standard device, C13860 | settings – Lenze E84Dxxxx User Manual
Page 80: Communication manual 8400 protec profibus
![background image](/manuals/565880/80/background.png)
EDS84DPBUS EN 2.0 - 09/2010
L
80
Communication manual 8400 protec PROFIBUS
Parameter reference
Parameters relevant for the communication
C13852
C13853
C13860
Parameter | Name:
C13852 | All words to standard device
Data type: UNSIGNED_16
Index: 10723
d
= 29E3
h
Display of the process data words 1 ... 16 which are transmitted from the master to the controller.
• Subcodes 1 ... 16 displays all process data words to the standard device.
Display area
(min. value | unit | max. value)
0
65535
Subcodes
Info
C13852/1
...
C13852/16
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13853 | All words from standard device
Data type: UNSIGNED_16
Index: 10722
d
= 29E2
h
Display of the process data words 1 ... 16 which are transmitted from the controller to the master.
• Subcodes 1 ... 16 displays all process data words from the standard device.
Display area
(min. value | unit | max. value)
0
65535
Subcodes
Info
C13853/1
...
C13853/16
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13860 | Settings
Data type: UNSIGNED_8
Index: 10715
d
= 29DB
h
Display of current configuration data.
Display area
(min. value | unit | max. value)
0
255
Subcodes
Info
C13860/1
PROFIsafe
• 0: Not active
• 1: Active
C13860/2
Number of process data words
• 1 ... 16 words
C13860/3
DRIVECOM parameter data channel
• 0: Not active
• 1: Active
C13860/4
Number of PROFIsafe words
• 0 or 4 words
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT