C13852 | all words to standard device, C13853 | all words from standard device, C13860 | settings – Lenze E84Dxxxx User Manual

Page 80: Communication manual 8400 protec profibus

Advertising
background image

EDS84DPBUS EN 2.0 - 09/2010

L

80

Communication manual 8400 protec PROFIBUS

Parameter reference

Parameters relevant for the communication

C13852

C13853

C13860

Parameter | Name:

C13852 | All words to standard device

Data type: UNSIGNED_16

Index: 10723

d

= 29E3

h

Display of the process data words 1 ... 16 which are transmitted from the master to the controller.

• Subcodes 1 ... 16 displays all process data words to the standard device.
Display area

(min. value | unit | max. value)

0

65535

Subcodes

Info

C13852/1
...
C13852/16

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13853 | All words from standard device

Data type: UNSIGNED_16

Index: 10722

d

= 29E2

h

Display of the process data words 1 ... 16 which are transmitted from the controller to the master.

• Subcodes 1 ... 16 displays all process data words from the standard device.
Display area

(min. value | unit | max. value)

0

65535

Subcodes

Info

C13853/1
...
C13853/16

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13860 | Settings

Data type: UNSIGNED_8

Index: 10715

d

= 29DB

h

Display of current configuration data.
Display area

(min. value | unit | max. value)

0

255

Subcodes

Info

C13860/1

PROFIsafe

• 0: Not active

• 1: Active

C13860/2

Number of process data words

• 1 ... 16 words

C13860/3

DRIVECOM parameter data channel

• 0: Not active

• 1: Active

C13860/4

Number of PROFIsafe words

• 0 or 4 words

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT