Parameters relevant for the communication

C13864

C13865

C13866

C13867

Parameter | Name:

C13864 | Active station address

Data type: UNSIGNED_8

Index: 10711

d

= 29D7

h

Display of active station address

• If the front panel DIP switches 1 to 64 are all in the "OFF" position (Lenze setting), the station address

parameterised under

C13899

becomes active and is displayed here after switching on.



Setting the station address ( 24)

Display area

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13865 | Display: Last PRM data

Data type: OCTET_STRING

Index: 10710

d

= 29D6

h

Display of the most recently sent parameter data from the PROFIBUS master with the "Set-Prm" telegram (ASCII

string with 24 digits)

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13866 | Display: Last CFG data

Data type: OCTET_STRING

Index: 10709

d

= 29D5

h

Display of the most recently sent configuration data from the PROFIBUS master with the "Chk-Cfg" telegram (ASCII

string with 22 digits)

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13867 | Display: Last diagnostic data

Data type: OCTET_STRING

Index: 10708

d

= 29D4

h

Display of the most recently sent diagnostic data to the PROFIBUS master (ASCII string with 16 digits)



Advanced diagnostic message ( 71)

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT