2 configuration of the host, Configuration of the host, Communication manual 8400 protec profibus – Lenze E84Dxxxx User Manual

Page 22

Advertising
background image

EDS84DPBUS EN 2.0 - 09/2010

L

22

Communication manual 8400 protec PROFIBUS

Commissioning

Configuration of the host

5.2

Configuration of the host

First the host system (master) must be configured to enable communication with the

controller.

Configuration for host system (master) and DP-V0 parameter data channel
To configure the PROFIBUS, the PROFIBUS device description file of the Inverter Drives 8400

protec must be read into the master.
The device description file is provided on the Lenze Internet pages in the "Services &

Downloads" area at:

www.Lenze.com

The following language variants of the device description file can be used:

LENZE84D.GSD (source file, English)

LENZE84D.GSG (German)

LENZE84D.GSE (English)

Defining the user data length
The user data length is defined during the initialisation phase of the master.
The Inverter Drives 8400 protec support the configuration of max. 16 process data words

(max. 32 bytes). By optionally activating the cycle parameter data channel, 4 process data

words (8 bytes) are additionally assigned. An additional 4 process data words are also

assigned if PROFISafe messages are transmitted.
The user data lengths for process input data and process output data are the same.

Advertising