Chapter 1 Introduction

10

EM920 Power Quality and Revenue Meter

harmonic and interharmonic voltage, mains signaling
voltage

• High-voltage fast transient recorder; impulsive and low

frequency oscillatory transient overvoltages with peaks
up to 2kV and durations from 20 microseconds

• Ready-for-use compliance statistics reports with the

supplementary software

Fault Recorder

• Digital Fault recorder: three voltage and three/four

current channels, up to 10 external digital triggers for
monitoring circuit breakers and protection relays;
onboard overcurrent and undervoltage fault detector;
zero-sequence voltage and current, voltage and
current unbalance; programmable fault thresholds and
hysteresis

• Up to 50 Amp fault currents

• Ready-for-use fault reports with the supplementary

software - fault current magnitudes and duration,
coincident volt magnitude, fault waveforms and fast
RMS trace

Event Recorder

• Event recorder for logging internal diagnostics events,

setpoint and I/O operations

Waveform Recorders

• Three fast Waveform recorders: up to 7 channels

simultaneous recording of three voltage and three/four
current channels

• Fixed and event-controlled recording time

• Selectable sampling rate of 32, 64, 128 or 256

samples per cycle; 1-20 pre-fault cycles; 0-2048 post-
fault cycles in event-controlled mode; up to 3 min of
continuous recording at a rate of 32 samples per cycle

• Optional 4-channel transient voltage recording at 1024

samples per cycle (with the transient add-on module)

• Synchronized waveforms from multiple devices in a

single plot

Exporting waveforms in COMTRADE and PQDIF file
formats

Data Recorders

• Sixteen Data recorders

• Programmable data logs on a periodic basis and on

any internal and external trigger; triggering from the
Fault recorder, PQ recorder or control setpoints;
exporting data trends in PQDIF file format

• Fast fault and PQ data profiling (trending) triggered

from the Fault and PQ recorders: 1/2-cycle to 10-min