Setpoint parameters, Appendix b, Appendix b setpoint parameters – SATEC EM920 Operation Manual User Manual

Page 201: Setpoint triggers, Setpoint actions

Advertising
background image

Appendix B Setpoint Parameters

EM920 Power Quality and Revenue Meter

201

Appendix B Setpoint Parameters

Setpoint Triggers

For setpoint triggers, see Appendix A Parameters for
Monitoring and Logging.

Setpoint Actions

The available setpoint actions are listed in the following table.

Setpoint Actions

Action Target

Description

NONE

No

action

SET EVENT FLAG

1-8

Set user event flag 1-8

CLEAR EVENT FLAG

1-8

Clear user event flag 1-8

OPERATE RELAY

1-7

Operate relay RO1-RO7

RELEASE RELAY

1-7

Release latched relay RO1-RO7

INCREMENT COUNTER

1-8

Increment counter 1-8

CLEAR COUNTER

1-8

Clear counter 1-8

RESET ALL COUNTERS

Clear all counters

RESET DEMANDS

ALL

Reset all engineering maximum demands

RESET DEMANDS

POWER

Reset engineering maximum power demands

RESET DEMANDS

VOLT/AMP

Reset maximum volts and ampere demand

RESET DEMANDS

VOLT

Reset maximum volt demand registers

RESET DEMANDS

AMP

Reset maximum ampere demand registers

RESET DEMANDS

HRM

Reset maximum harmonic demand registers

RESET TOU DEMANDS

Reset billing/TOU maximum demands (end of billing period)

CLEAR MIN/MAX LOG

Clear Min/Max log

EVENT LOG

OPER

Event log on setpoint operated

EVENT LOG

RELS

Event log on setpoint released

EVENT LOG

ANY

Event log on any setpoint transition

DATA LOG

1-14

Conventional data log 1-14

WAVEFORM LOG

1-2

Waveform Log 1-2

SEND NOTIFICATION

Send a notification message to a remote TCP server

Advertising