Chapter 5 Configuring the EM920

Configuring the EN50160 Recorders

126

EM920 Power Quality and Revenue Meter

Option Range

Default

Description

Rapid Voltage Changes

Repetition Rate

1-10

1

Defines the maximum repetition rate in
variations per hour (equal or less than)
for rapid voltage changes. Voltage
changes at higher rates are not classified

since they will be subject for flicker.

Flicker

Pst Period

1-10 min

10 min

Defines the period of time for the short-
term flicker evaluation. The standard
setting of 10 minutes can be temporarily
changed in the device for testing

purposes.

Harmonic Voltage

THD, up to order

25-50

40

Defines the highest harmonic order

included in the THD evaluation.

Harmonics, up to

order

25-50

25

Defines the highest harmonic order for

evaluation of the harmonic voltages.

Interharmonic Voltage

Evaluation Disabled,

Enabled

Disabled

Enables the evaluation of the
interharmonic voltages

THD, up to order

25-50

40

Defines the highest interharmonic order
included in the THD evaluation.

Interharmonics, up
to order

25-50

25

Defines the highest harmonic order for
evaluation of the interharmonic voltages.

Mains Signaling Voltage

Evaluation Disabled,

Enabled

Disabled

Enables the evaluation of the mains
signaling voltages

1st Signaling
Frequency

110-3000 Hz

183.0 Hz

Specifies the mains signaling frequency
for the compliance evaluation

2nd Signaling
Frequency

110-3000 Hz

191.0 Hz

Specifies the mains signaling frequency
for the compliance evaluation

3rd Signaling

Frequency

110-3000 Hz

217.0 Hz

Specifies the mains signaling frequency

for the compliance evaluation

4th Signaling

Frequency

110-3000 Hz

317.0 Hz

Specifies the mains signaling frequency

for the compliance evaluation

Transient Overvoltage

Detection and
Classification Method

Peak voltage
Impulsive voltage

Peak voltage Defines the method for detecting and

classifying transient overvoltages:
Peak voltage – transient overvoltages are
classified by the peak voltage;
Impulsive voltage - transient overvoltages
are classified by the impulse amplitude.

Clearing EN50160 Evaluation Counters

See

Reset of Accumulators and Log Files

in Chapter 6 on how

to clear the present contents of the EN50160 evaluation
counters before starting your EN50160 evaluation.