SATEC EM920 Operation Manual User Manual

Page 209

Advertising
background image

Appendix E EN50160 Statistics Log Files

EM920 Power Quality and Revenue Meter

209

Field No.

Designation Description

8

V2 Plt Max

Maximum Plt on phase V2

9

V3 N1

Number of incidents Plt > 1% on phase V3

10

V3 Plt Max

Maximum Plt on phase V3

Voltage

Dips

(indicative statistics)

1

N11 90%/100ms Number of polyphase incidents u<90%/t<100ms

2

N12 85%/100ms Number of polyphase incidents u<85%/t<100ms

3

N13 70%/100ms Number of polyphase incidents u<70%/t<100ms

4

N14 40%/100ms Number of polyphase incidents u<40%/t<100ms

5

N11 90%/500ms Number of polyphase incidents u<90%/t<500ms

6

N12 85%/500ms Number of polyphase incidents u<85%/t<500ms

7

N13 70%/500ms Number of polyphase incidents u<70%/t<500ms

8

N14 40%/500ms Number of polyphase incidents u<40%/t<500ms

9

N11 90%/1s

Number of polyphase incidents u<90%/t<1s

10

N12 85%/1s

Number of polyphase incidents u<85%/t<1s

11

N13 70%/1s

Number of polyphase incidents u<70%/t<1s

12

N14 40%/1s

Number of polyphase incidents u<40%/t<1s

13

N11 90%/3s

Number of polyphase incidents u<90%/t<3s

14

N12 85%/3s

Number of polyphase incidents u<85%/t<3s

15

N13 70%/3s

Number of polyphase incidents u<70%/t<3s

16

N14 40%/3s

Number of polyphase incidents u<40%/t<3s

17

N11 90%/20s

Number of polyphase incidents u<90%/t<20s

18

N12 85%/20s

Number of polyphase incidents u<85%/t<20s

19

N13 70%/20s

Number of polyphase incidents u<70%/t<20s

20

N14 40%/20s

Number of polyphase incidents u<40%/t<20s

21

N11 90%/60s

Number of polyphase incidents u<90%/t<60s

22

N12 85%/60s

Number of polyphase incidents u<85%/t<60s

23

N13 70%/60s

Number of polyphase incidents u<70%/t<60s

24

N14 40%/60s

Number of polyphase incidents u<40%/t<60s

25

N11 90%/180s

Number of polyphase incidents u<90%/t<180s

26

N12 85%/180s

Number of polyphase incidents u<85%/t<180s

27

N13 70%/180s

Number of polyphase incidents u<70%/t<180s

28

N14 40%/180s

Number of polyphase incidents u<40%/t<180s

29

V1 N1

Total number of incidents on phase V1

30

V1 Min

Minimum residual voltage on phase V1

31

V2 N1

Total number of incidents on phase V2

32

V2 Min

Minimum residual voltage on phase V2

33

V3 N1

Total number of incidents on phase V3

34

V3 Min

Minimum residual voltage on phase V3

Voltage

Interruptions

(indicative statistics)

1

N1 1s

Number of polyphase incidents t<1s

2

N2 180s

Number of polyphase incidents t<180s

3

N3 >180s

Number of polyphase incidents t>180s

4

V1 Min

Minimum residual voltage on phase V1

5

V2 Min

Minimum residual voltage on phase V2

6

V3 Min

Minimum residual voltage on phase V3

Temporary

Overvoltages (indicative statistics)

1

N11 110%/1s

Number of polyphase incidents u>110%/t<1s

2

N12 120%/1s

Number of polyphase incidents u>120%/t<1s

3

N13 140%/1s

Number of polyphase incidents u>140%/t<1s

4

N14 160%/1s

Number of polyphase incidents u>160%/t<1s

5

N15 200%/1s

Number of polyphase incidents u>200%/t<1s

Advertising