Appendix E EN50160 Statistics Log Files

212

EM920 Power Quality and Revenue Meter

Field No.

Designation Description

10

V1 H#

Worst-case interharmonic component number on phase V1

11

V1 THD Max

Worst-case interharmonic voltage THD on phase V1

12

V2 N1

Number of interharmonic voltage incidents on phase V2

13

V2 N2

Number of interharmonic voltage THD incidents on phase V2

14

V2 HD% Max

Worst-case interharmonic magnitude on phase V2, %Un

15

V2 H#

Worst-case interharmonic component number on phase V2

16

V2 THD Max

Worst-case interharmonic voltage THD on phase V2

17

V3 N1

Number of interharmonic voltage incidents on phase V3

18

V3 N2

Number of interharmonic voltage THD incidents on phase V3

19

V3 HD% Max

Worst-case interharmonic magnitude on phase V3, %Un

20

V3 H#

Worst-case interharmonic component number on phase V3

21

V3 THD Max

Worst-case interharmonic THD on phase V3

Mains

Signaling

Voltage

1

Nnv

Number of non-valid 3-sec intervals

2

N

Number of valid 3-sec intervals

3

N1

Number of polyphase incidents, N1

4

N1/N, %

EN50160 compliance ratio, N1/N

5

V1 N1

Number of incidents on phase V1

6

V1 Frq1 %Un

Maximum 1st signaling voltage magnitude on phase V1, %Un

7

V1 Frq2 %Un

Maximum 2nd signaling voltage magnitude on phase V1, %Un

8

V1 Frq3 %Un

Maximum 3rd signaling voltage magnitude on phase V1, %Un

9

V1 Frq4 %Un

Maximum 4th signaling voltage magnitude on phase V1, %Un

10

V2 N1

Number of incidents on phase V2

11

V2 Frq1 %Un

Maximum 1st signaling voltage magnitude on phase V2, %Un

12

V2 Frq2 %Un

Maximum 2nd signaling voltage magnitude on phase V2, %Un

13

V2 Frq3 %Un

Maximum 3rd signaling voltage magnitude on phase V2, %Un

14

V2 Frq4 %Un

Maximum 4th signaling voltage magnitude on phase V2, %Un

15

V3 N1

Number of incidents on phase V3

16

V3 Frq1 %Un

Maximum 1st signaling voltage magnitude on phase V3, %Un

17

V3 Frq2 %Un

Maximum 2nd signaling voltage magnitude on phase V3, %Un

18

V3 Frq3 %Un

Maximum 3rd signaling voltage magnitude on phase V3, %Un

19

V3 Frq4 %Un

Maximum 4th signaling voltage magnitude on phase V3, %Un

20

Frq1

1st signaling voltage frequency

21

Frq2

2nd signaling voltage frequency

22

Frq3

3rd signaling voltage frequency

23

Frq4

4th signaling voltage frequency

EN50160 Harmonics Survey Log (Data Log #10)

Field No.

Designation Description

V1

Harmonic

Voltage

1

THD MAX

Maximum THD

2

THDO MAX

Maximum odd harmonics THD

3

THDE MAX

Maximum even harmonics THD

4

%HD02 MAX

Maximum H02 harmonic voltage magnitude, %Un

5

%HD03 MAX

Maximum H03 harmonic voltage magnitude, %Un

… …

52

%HD50 MAX

Maximum H50 harmonic voltage magnitude, %Un

V2

Harmonic

Voltage

1

THD MAX

Maximum THD

2

THDO MAX

Maximum odd harmonics THD

3

THDE MAX

Maximum even harmonics THD

Advertising