Chapter 5 Configuring the EM920

General Meter Setup

90

EM920 Power Quality and Revenue Meter

Configuring Analog Outputs

The EM920 can provide one AO expansion module with a total
of 4 analog outputs with options for 0-1 mA, ±1mA, 0-20 mA
and 4-20 mA.

To configure the analog outputs, select General Setup from
the Meter Setup menu, and then click on the Analog Outputs
tab. The setup entries will be blanked if the AO expansion
module is not installed in the meter.

The available analog output options are described in the
following table.

Option Range

Description

AO type

0-1mA
±1mA
0-20mA
4-20mA

The analog output type. When connected to the
meter, shows the actual AO type received from
the device. When working off-line, select the
analog output option corresponding to your

analog module.

Output parameter

See Appendix C

Selects the measured parameter to be
transmitted through the analog output channel.

Zero scale

Defines the low engineering scale (in primary
units) for the analog output corresponding to a

lowest (zero) output current (0 or 4 mA)

Full scale

Defines the high engineering scale (in primary
units) for the analog output corresponding to a

highest output current (1 or 20 mA)