Chapter 5 Configuring the EM920

General Meter Setup

EM920 Power Quality and Revenue Meter

75

NOTE

Test Mode options and other device options have different
security levels. You may not be allowed to change the device
options if the user password you provided does not have
required permissions.

The following table lists available device options.

Display

Label

Parameter Options Default

Description

Power/Energy Options

Power Mode

Power Calculation
Mode

S=f(P, Q) (reactive
power mode),
Q=f(S, P) (non-
active power

mode)

S=f(P, Q)

The method used for calculating
reactive and apparent powers (see

“Power Calculation Modes” below)

Energy Roll

Energy Roll Value,
kWh

1000.0
10000.0
100000.0
1000000.0
10000000.0
100000000.0

100000000.0 The value at which energy

counters roll over to zero

End of Bill

End of Billing
Period

Auto (monthly)
Auto/COM
Auto/COM/Manual
COM
Manual

Auto
(monthly)

Triggering an end of billing period:
Auto – monthly self-reading
COM – remote via communications
Manual – from the front display

Tariff Control Tariff Control

Calendar
Communication
Tariff inputs
D1…D10

1

Defines the tariff switching method

(see “Tariff Control” below).

Num Tariffs

Number of tariffs

1-8

1

Defines the number of season tariff
rates when no TOU calendar

schedule is available

Transf.
Correction

OFF

(disabled)

ON (enabled)

OFF

Enables instrument transformer
correction – only via the front

display

Loss

Compensation

OFF

(disabled)

ON (enabled)

OFF

Enables transformer/line loss
compensation – only via the front

display

Demand Forgiveness (Cold Load Pickup)

Dmd. Delay

Demand Delay,
min

0-60 min
0=disabled

0

The forgiveness time after an
outage that the meter will not
calculate or log the maximum

demands

Min. Outage
Duration

Minimum Outage
Duration, s

0-900 s

0

The minimum power outage
duration to apply the demand

forgiveness time

Test Mode

Test Mode

Energy LED Test

OFF (disabled)
ON (enabled)

Disabled

Setting this option puts the meter

into TEST mode

Pulse

Constant

Energy LED pulse

rate, Wh/impulse

0.01-0.25 Wh/imp
(100,000 – 4,000
imp/kWh)

0.10 Wh/imp
(10,000

imp/kWh)

Test LED pulse constant - the
amount of accumulated energy (in
secondary units) giving one pulse

via “WATT” and “VAR” LEDs

Data Scales

N/A

Volts Scale, V

60-600 V

144 V

The maximum voltage scale
allowed, in secondary volts. See

Data Scales

in Appendix G

N/A

Amps Scale, A

1.0 – 50.0

4A/20 A

The maximum current scale
allowed, in secondary amps. See

Data Scales

in Appendix G