SATEC EM920 Operation Manual User Manual

Page 71

Advertising
background image

Chapter 5 Configuring the EM920

Configuring Communications

EM920 Power Quality and Revenue Meter

71

Parameter Options

Default Description

Client Enabled

NO, YES

NO

Enables operations of the

notification client

Server IP Address

192.168.0.3

The IP address of the
notification server

Server Port

0-65535

502

The TCP service port of the
notification server

Message Exchange
Address

0-65535 1000

Connection via Network Ethernet,

GPRS/Modem

Automatically

selected

depending on the network

module installed

Client connections are triggered via programmable setpoints.
To send event notifications to a server, configure a setpoint
to respond to desired triggers or to periodic time events and
add the "Send notification" action to the end of the setpoint
actions list (see

Using Control Setpoints

).

Setpoint operation events triggered by regular analog and
digital triggers are reported twice - when the event starts and
when it ends, except of the pulsed events and time triggers
that will be reported once.

In case of triggering notifications with events generated by
the PQ and Fault recorders, like the PQ EVENT, FAULT EVENT,
EXTERNAL TRIGGER or FAULT DETECTED triggers, the
recorded power quality or/and corresponding fault events are
reported instead of setpoint-triggered notifications. If regular
triggers are added to the setpoint triggers list, then the
setpoint operation events will also be reported.

Advertising