Daylight saving time, Time synchronization sources – SATEC EM920 Operation Manual User Manual

Page 82

Advertising
background image

Chapter 5 Configuring the EM920

General Meter Setup

82

EM920 Power Quality and Revenue Meter

Display Label

Parameter

Options

Default

Description

Daylight Daylight

saving

time (DST)

Disabled
Enabled
Scheduled

Disabled

Disabled: the RTC operates in
standard time only.
Enabled: the time is automatically
updated at the predefined fixed

DST switch dates.
Scheduled: the time is
automatically updated at the
calendar scheduled DST switch

dates.

Start Month

DST Start Month January-

December

March

The month when DST begins.

Start Week

DST Start Week

First, Second,
Third, Fourth,

Last

Second

The week when DST begins.

Start Day

DST Start Day

Sunday-

Saturday

Sunday

The day when DST begins.

Start Hour

DST Start Hour

1-6

2

The hour when DST begins.

End Month

DST End Month

January-
December

November The month when DST ends.

End Week

DST End Week

First, Second,
Third, Fourth,

Last

First

The week when DST ends.

End Day

DST End Day

Sunday-

Saturday

Sunday

The day when DST ends.

End Hour

DST End Hour

1-6

2

The hour when DST ends.

Date Order

Date Order

MM/DD/YY
DD/MM/YY
YY/MM/DD

MM/DD/YY The display date order

Clock Sync

Time
synchronization

input

None
IRIG-B
SNTP
DI1…DI10 1PPM
DI1…DI2 1PPS

None

The external port receiving the time

synchronization signal

Daylight Saving Time

By default, the daylight saving time option is disabled in the
EM920.

When the DST option is enabled, the meter automatically
adjusts the clock at the predefined start/end time when
daylight savings time begins/ends.

When the DST option is set to Scheduled mode, the only DST
start/end hours are used, while the DST switch dates are
taken from the TOU calendar (see

Configuring the Season

Tariff and DST Schedule

). If the DST switch dates are not

found in the calendar for the present year, the meter will use
the dates you defined in your Local Settings.

When the daylight savings option is disabled, the device clock
should be manually adjusted for daylight saving time.

Time Synchronization Sources

The EM920 can synchronize its clock with a remote SNTP
server via the Internet, or receive the time synchronization
signal either from a GPS clock with an IRIG-B time-code
output, or from an external device providing second-aligned
(1PPS) or minute-aligned (1PPM) pulses.

Advertising