Chapter 2 Operating the EM920

Operating Digital Inputs

24

EM920 Power Quality and Revenue Meter

Operating Digital Inputs

The EM920 can monitor a total of 10 digital inputs including
two fast internal digital inputs and 8 inputs found on the 8DI
expansion module. See the EM920 Installation Manual for
digital input ratings and connection diagrams.

Fast internal digital inputs are sampled at a 1-ms rate, and
expansion inputs are sampled at a 1/2-cycle rate.

Digital inputs functionality is programmable in the EM920 and
any digital input can perform multiple metering and control
functions at the same time:

• Receiving energy pulses from external watt meters

(sub metering) – link a digital input to a Billing/TOU
register and provide a required multiplication factor
(see

Configuring Billing/Tariff Registers

in Chapter 5)

• Counting pulses from external pulse sources – link a

digital input to a pulse counter (see

Using Counters

in

Chapter 5)

• Triggering a setpoint – put a digital input into a

setpoint trigger list (see

Using Control Setpoints

in

Chapter 5)

• Triggering the Fault Recorder – link a digital input to

the Fault Recorder (see

Configuring Digital Inputs

in

Chapter 5) and enable external triggers in the Fault
Recorder setup (see

Configuring the Fault Recorder

in

Chapter 5)

• External synchronization of power demand intervals –

select a digital input as an external power demand
sync source (see

Basic Meter Setup

in Chapter 5)

• External synchronization of the meter clock – select a

digital input as a time synchronization input (see

Local

Settings

in Chapter 5) and provide 1PPS or 1PPM

pulses from the external master clock source.

All digital inputs have a user-programmable debounce time
from one to 100 milliseconds. See

Configuring Digital Inputs

in Chapter 5 on how to configure digital inputs in your meter.

Operating Relay Outputs

Up to seven relay outputs can be provided in your EM920
including one on-board KYZ relay output and six additional
outputs on the 6RO expansion module. See the EM920
Installation Manual for available relay output ratings and
connections.

All relay outputs are updated at a half-cycle rate.

Each relay is independently programmable in the EM920 and
can operate in latched, unlatched, pulse or KYZ mode.

Relay operations can be inverted so that the relay is
energized in its non-active state and de-energized when it is
operated. This mode, known as “failsafe” mode, may be used
for signaling purposes to send alarms when the device is not
operational either due to a fault or due to loss of power.