Configuring digital inputs, Igure digital inputs in your meter – SATEC EM920 Operation Manual User Manual

Page 86

Advertising
background image

Chapter 5 Configuring the EM920

General Meter Setup

86

EM920 Power Quality and Revenue Meter

Configuring Digital Inputs

The EM920 has two embedded digital inputs (DI1-DI2) and
can provide one additional expansion module with a total of 8
digital inputs (DI3 through DI10). I/O numbers are
automatically assigned to the inputs.

To configure the digital inputs, select General Setup from the
Meter Setup menu, and then click on the Digital Inputs tab.
Digital inputs that are not present in your meter are not
shown.

The available options are shown in the following table.

Parameter Options Default

Description

Pulse input mode PULSE MODE

KYZ MODE

PULSE
MODE

Pulse mode: either leading, or trailing
edge of the input pulse is recognized as

an event.
KYZ mode: both leading and trailing
edges of the input pulse are recognized

as separate events.

Pulse polarity

NORMAL (N.O.)
INVERTING
(N.C.)

NORMAL

Normal polarity: the open to closed

transition is considered a pulse.
Inverting polarity: the closed to open
transition is considered a pulse. It has no
meaning in KYZ mode where both

transitions are effective.

Debounce time

1-1000 ms

10 ms

The amount of time while the state of the
digital input should not change to be
recognized as a new state. Too low
debounce time could produce multiple

events on the input change.