Configuring the fault recorder, In chapter 5 f, Configuring the fault – SATEC EM920 Operation Manual User Manual

Page 117: Recorder

Advertising
background image

Chapter 5 Configuring the EM920

Configuring Recorders

EM920 Power Quality and Revenue Meter

117

Configuring the Fault Recorder

The Fault recorder automatically records all fault events to
the Fault log file. It can be triggered via the embedded fault
detector, or externally through any of the 8 digital inputs.

The Fault recorder can be globally disabled or enabled in your
meter.

The Fault recorder setup allows you to adjust thresholds and
hysteresis for different fault triggers, and to define the
waveform and data log options for synchronous recording
during fault events.

To configure the Fault recorder:

1. Select Memory/Log from the Meter Setup menu, and

then click on the Fault Recorder tab.

2. Enable fault triggers suitable for your application.

3. If you wish to change the default settings, adjust

thresholds and hysteresis for your fault triggers.

4. Select the waveform and data logging options for fault

events.

5. Download your setup to the device.

The following table lists available Fault recorder options.

Option Range

Default

Description

Thresholds

Threshold, % 0-200.0%

Defines the operating threshold for a fault trigger in
percent of the nominal (reference) value

Threshold,

secondary

Shows the setup value in secondary units for the

selected operating threshold