Chapter 5 Configuring the EM920

Configuring Communications

70

EM920 Power Quality and Revenue Meter

Parameter Options

Default Description

XPW Client Enabled

NO, YES

NO

Enables operations of the
eXpertPower client

Time to Next Session,
min

1-99999

The time remaining to the
next connection session

Connection via Network Ethernet,

GPRS/Modem

Ethernet Automatically

selected

depending on the network

module installed

NOTES

1. Do not enable the eXpertPower client in your meter if

you do not use the eXpertPower

TM

service.

2. Do not change the connection period setting. The

eXpertPower server updates it automatically.

Setting-Up TCP Notification Client

Select Communication Setup from the Meter Setup menu,
and then click on the TCP Notification Client Setup tab.

The TCP notification client can establish connections with a
remote Modbus/TCP server and send notification messages
either on events, or periodically on a time basis. See the
EM920 Modbus Reference Guide for more information on the
client operation and the notification message layout.

The server’s IP address, port number and starting Modbus
register address are programmable in the meter.

The following table lists available options.