Appendix F EN50160 Evaluation and Recording

214

EM920 Power Quality and Revenue Meter

Appendix F EN50160 Evaluation and Recording

EN50160 Background

The EN50160 European standard “Voltage characteristics of
electricity supplied by public distribution systems” issued by
CENELEC defines the main physical characteristics of electric
energy supplied by low and medium voltage public
distribution systems under normal operating conditions.

The voltage characteristics are evaluated using a statistical
approach. The standard and its referenced publications
specify for each voltage characteristic:

• Method of evaluation

• Integrating interval for a single measurement

• Observation period

• Statistical indication of the probability of not exceeding

a specified limit

• Standard compliance limits or indicative values within

which any customer can expect the voltage
characteristics to remain

Compliance Limits

For some voltage characteristics, the standard provides
definite limits that can be complied with for most of the time
considering the possibility of relatively rare excursions
beyond these limits. Limits are set with a view to compliance
for a percentage of the observation time, e.g. 95% of the
observations in any period of one week.

The following table gives the characteristics for which definite
limits have been specified by the standard.

Indicatives Values

For the remaining characteristics of the voltage, by their
unpredictable nature, the standard gives only indicative

Voltage characteristic

Compliance with stated

limits, % of time

Observation

period

Power frequency

±1% for 95% of a week
±1% for 99.5% of a year
+4/-6% for 100% of time

Week, year

Voltage variations (supply

voltage magnitude)

±10% Un for 95% of time

Week

Rapid voltage changes

≤4-5% Un (up to 10% Un) Day

Flicker (fluctuations of
voltage magnitude)

Plt ≤ 1 for 95% of time

Week

Voltage unbalance

≤2-3% for 95% of time

Week

Harmonic voltage

THD ≤ 8 for 95% of time

Week

Interharmonic voltage

To be defined

Week

Mains signaling voltage

Within “Meister-curve” for
99% of time

Day