Instrument Transformer Correction Setup

Transformer correction allows you to compensate ratio and
phase angle inaccuracies of the voltage and current
instrument transformers.

Select General Setup from the Meter Setup menu, and then
click on the Transformer Correction tab.

The available options are listed in the following table.

Parameter Options

Description

Channel

None, V1-V3, I1-I4 Voltage/current

channel

Test Point, %

5-200%

Percent of the nominal (rated) voltage/current at
which the ratio correction factor and phase angle

error are specified

Ratio Correction Factor

0.900-1.100

The ratio of the true transformer ratio to the

marked ratio