General Meter Setup

EM920 Power Quality and Revenue Meter

95

Using Control Setpoints

The EM920 has an embedded logical controller that runs
different actions in response to user-defined internal and
external events. Unlike a PLC, the EM920 uses a simplified
programming technique based on setpoints that allows the
user to define a logical expression based on measured analog
and digital values that produces a required action.

The EM920 provides 16 control setpoints with programmable
operate and release delays. Each setpoint evaluates a logical
expression with up to four arguments using OR/AND logic.
Whenever an expression is evaluated as “true”, the setpoint
performs up to four concurrent actions that can send a
command to the output relays, increment or decrement a
counter, or trigger a recorder.

To program the setpoints, select General Setup from the
Meter Setup menu, and then click on the Control/Alarm
Setpoints tab.

The available setpoint options are described in the following
table:

Option Format/Range

Description

Setpoint Triggers

OR/AND

OR, AND

The logical operator for the trigger

Input group

The trigger parameter group (see Appendix A)

Trigger

parameter

The trigger parameter that is used as an argument

in the logical expression (see Appendix A)