SATEC EM920 Operation Manual User Manual

Page 115

Advertising
background image

Chapter 5 Configuring the EM920

Configuring Recorders

EM920 Power Quality and Revenue Meter

115

The following table lists available waveform options.

Parameter Options

Description

Recording Time

Fixed
Event-controlled

Fixed – a waveform is recorded up

to the maximum specified length
Event-controlled – a waveform extends
for as long as trigger conditions exist
plus post-event time, or up to the

maximum specified length

Samples per Cycle

32, 64, 128, 256, 1024

Waveform sampling rate

Max. Cycles per
Event

16-10848 at 32 samples/cycle
8-5424 at 64 samples/cycle
4-2712 at 128 samples/cycle
2-1356 at 256 samples/cycle
1 at 1024 samples/cycle

The maximum waveform length per
event in cycles including pre-event and

post-event time

Pre-event Cycles

1-20

Pre-event time in cycles to be recorded
prior to event

Post-event Cycles

0-2048

Post-event time in cycles to be
recorded after end of event in event-

controlled mode

Num. of Channels

1-7

The number of simultaneously recorded

channels (informative)