Chapter 5 Configuring the EM920

General Meter Setup

EM920 Power Quality and Revenue Meter

73

Display Label

Parameter

Options

Default

Description

Nom. Voltage

PT Secondary (L-L)

Voltage

50-480 V

120 V

The nominal secondary line-to-
line voltage. Used as a
reference voltage for the

EN50160 evaluation.

CT Primary

CT Primary Current

1

1-20,000 A

5 A

The primary rating of the phase
current transformer

CT4 Primary

I4 CT Primary
Current

1-20,000 A

5 A

The primary rating of the I4
current transformer

Nom.
Frequency

Nominal Frequency

50, 60 Hz

60 Hz

The nominal line frequency

Demand Setup

Power Dmd.
Period

Power block demand
period

1, 2, 3, 5, 10,
15, 20, 30, 60

min

15 min

The length of the demand
period for power demand

calculations.

Num. Dmd.
Periods

Number of Blocks in
Sliding Demand

1-15

1

The number of blocks to be
averaged for sliding window

demands

Dmd. Sync.
Source

Power Demand Sync
Source

Meter clock,
DI1-DI10

Meter
clock

The source input for
synchronization of the demand
intervals. If a digital input is
selected as the source, a pulse
front denotes the start of the

demand interval

Volt. Dmd.
Period

Volt Demand Period 0-9000 sec

900 sec

The length of the demand
period for volt demand

calculations

Amp. Dmd.

Period

Ampere Demand

Period

0-9000 sec

900 sec

The length of the demand
period for ampere demand

calculations

Hrm. Dmd.
Period

THD Demand Period 0-9000 sec

900 sec

The length of the demand
period for THD demand

calculations

TDD Setup

Max. Dmd.
Load

I Max. Load Current 0 – 20,000 A

0 = CT primary

0

The maximum demand load
current for phase current inputs

I4 Max. Dmd.
Load

I4 Max. Load Current 0 – 20,000 A

0 = CT primary

0

The maximum demand load
current for I4 current input

1

The maximum value for the product of the CT primary current

and PT ratio is 57,500,000. If the product is greater, power

readings are zeroed.

Available wiring modes are listed in the following table.

Wiring Mode

Description

3OP2

3-wire Open Delta using 2 CTs (2 element)

4LN3

4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings

3DIR2

3-wire Direct Connection using 2 CTs (2 element)

4LL3

4-wire Wye using 3 PTs (3 element), line-to-line voltage readings

3OP3

3-wire Open Delta using 3 CTs (2½ element)

3LN3

4-wire Wye using 2 PTs (2½ element), line-to-neutral voltage readings

3LL3

4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings


NOTE

In 4LN3 and 3LN3 wiring modes, the voltage readings for volt
demands represent line-to-neutral voltages; otherwise, they
will be line-to-line voltages. The voltage waveforms and
harmonics in 4LN3 and 3LN3 wiring modes represent line-to-
neutral voltages; otherwise, they will be line-to-line voltages.