Chapter 5 Configuring the EM920

Configuring Communication Protocols

EM920 Power Quality and Revenue Meter

133

• Less than (under) - a new event is generated when

the point value drops below the specified threshold,

and then when it returns above the threshold plus a
predefined return hysteresis – applicable for AI

objects.

Hysteresis for the return threshold is 0.05 Hz for
frequency and 2% of the operating threshold for all
other points.

4. Check the “Ev On” box for the points you wish to be

included into event poll reports.

5. In the “Ev Class” box, select the event poll class for

the change event points.

6. Repeat these steps for all points you want to be

monitored for events.

7. Click Send to download your setup to the device.