Appendix G Data Scales

224

EM920 Power Quality and Revenue Meter

Appendix G Data Scales

The maximum values for volts, amps and powers in the
EM920 setup and in communications are limited by the
voltage and current scale settings. See

Device Options and

Mode Control

in Chapter 5 on how to change the voltage and

current scales in your meter.

The following table shows the meter data scales.

Scale Range

Maximum voltage (V max)

Voltage scale × PT Ratio, V

1

Maximum current (I max)

Current scale × CT Ratio, A

2, 3

Maximum Power (P max)

4

V max × I max × 2, W

Maximum frequency

100 Hz

1

The default voltage scale is 144V (120V+20%).

2

CT Ratio = CT primary current/CT secondary current

3

The default current scale is 4 × CT secondary (4.0A with 1A

secondaries and 20.0A with 5A secondaries).

4

Maximum power is rounded to whole kilowatts. With

PT=1.0, it is limited to 9,999,000 W.