Display features, No load/power flow direction indicator, Phase presence indicators – SATEC EM920 Operation Manual User Manual

Page 34: Backlight

Advertising
background image

Chapter 3 Using Front Display

Display Operations

34

EM920 Power Quality and Revenue Meter

Indicator

Icon

Event

Priority

Description

Low

General diagnostic message indicator: indicates
that there are diagnostic messages you can

inspect via the DIAGNOSTICS display.
The icon is shut down after you explicitly reset
diagnostics messages either from the display or
via communications (see

Clearing Device

Diagnostics

).

You can disable diagnostic message indicator via
the Display Setup menu (see

Display Setup

).

No Load/Power Flow Direction Indicator

The power flow indicator gives information on the load
presence and shows the direction of active power.

Indicator

Icon

Description

No load.

Direct active power flow – delivered active energy.

Reversed active power flow – received active energy.

Phase Presence Indicators

Phase presence indicators “ABC” show the status of either
Va-Vb-Vc phase-to-neutral voltages in line-to-neutral wiring
modes, or Vab-Vbc-Vca phase-to-phase voltages in line-to-
line wiring modes.

Indicator

Icon

Description

All voltages are present and above the voltage dip threshold.

Blinking phase indicator – the phase voltage is below the
defined voltage dip threshold. Possibly indicates an incorrect
meter nominal voltage setting (see

Basic Meter Setup

in

Chapter 5).

Dashed phase indicator - the phase voltage is either missing or

below the voltage interruption threshold.

If the phase voltage is below the defined voltage dip
threshold, its corresponding phase indicator is blinking.

If the phase voltage is either missing or below the voltage
interruption threshold, the phase indicator is replaced with a
dash.

Display Features

The EM920 display has a number of programmable features
that can be disabled, enabled and adjusted via the meter
Display Setup (see

Display Setup

in Chapter 5).

Backlight

A short press on any button while the display backlight is off
switches the backlight on.

The backlight stays on as long as you selected in the display
setup and then dims to conserve power. The backlight time is
factory set to 1 minute and can be programmed from 1 to 10

Advertising