The following tables list the EN50160 evaluation parameters
recorded by the device to the EN50160 statistics data log
files. The second column shows data abbreviations used in
the PAS data log reports. Data log file sections are
highlighted in bold.

EN50160 Compliance Statistics Log (Data Log #9)

Field No.

Designation Description

Power

Frequency

1

Nnv

Number of non-valid 10-sec intervals

2

N

Number of valid 10-sec intervals

3

N1

Number of incidents ±1%, N1

4

N2

Number of incidents +4%/-6%, N2

5

N1/N, %

EN50160 compliance ratio, N1/N

6

N2/N, %

EN50160 compliance ratio, N2/N

7

Freq Min

Minimum frequency

8

Freq Max

Maximum frequency

Supply

Voltage

Variations

1

Nnv

Number of non-valid 10-min intervals

2

N

Number of valid 10-min intervals

3

N1

Number of polyphase incidents ±10%, N1

4

N2

Number of polyphase incidents +10/-15%, N2

5

N1/N, %

EN50160 compliance ratio, N1/N

6

N2/N, %

EN50160 compliance ratio, N2/N

7

V1 N1

Number of incidents ±10% on phase V1

8

V1 Min

Minimum voltage on phase V1

9

V1 Max

Maximum voltage on phase V1

10

V2 N1

Number of incidents ±10% on phase V2

11

V2 Min

Minimum voltage on phase V2

12

V2 Max

Maximum voltage on phase V2

13

V3 N1

Number of incidents ±10% on phase V3

14

V3 Min

Minimum voltage on phase V3

15

V3 Max

Maximum voltage on phase V3

Rapid

Voltage

Changes

1

N1

Number of polyphase incidents

2

V1 N1

Number of incidents on phase V1

3

V1 dV%

Maximum voltage variation on phase V1, dV/Un%

4

V2 N1

Number of incidents on phase V2

5

V2 dV%

Maximum voltage variation on phase V2, dV/Un%

6

V3 N1

Number of incidents on phase V3

7

V3 dV%

Maximum voltage variation on phase V3, dV/Un%

Flicker

1

Nnv

Number of non-valid 2-hour intervals

2

N

Number of valid 2-hour intervals

3

N1

Number of polyphase incidents Plt >1%, N1

4

N1/N, %

EN50160 compliance ratio, N1/N

5

V1 N1

Number of incidents Plt > 1% on phase V1

6

V1 Plt Max

Maximum Plt on phase V2

7

V2 N1

Number of incidents Plt > 1% on phase V2

Advertising