Configuring communication protocols, Configuring modbus, Modbus point mapping – SATEC EM920 Operation Manual User Manual

Page 127: En50160 harmonics limits setup

Advertising
background image

Chapter 5 Configuring the EM920

Configuring Communication Protocols

EM920 Power Quality and Revenue Meter

127

Configuring Communication Protocols

This section describes how to customize protocol options for
use with your application software.

Configuring Modbus

Modbus Point Mapping

The EM920 provides 120 user assignable registers in the
address range of 0 to 119. You can re-map any register
available in the device to any assignable register so that
Modbus registers that reside at different locations may be
simply accessed using a single request by re-mapping them
to adjacent addresses.

Initially these registers are reserved and none of them points
to an actual data register.

To build your own Modbus register map:

1. From the Meter Setup menu select Protocol Setup and

click on the Modbus Registers tab.

2. Click on the Default button to cause the assignable

registers to reference the actual default device register
11776 (0 through 119 are not allowable register
addresses for re-mapping).

3. Type in the actual addresses you want to read from or

write to via the assignable registers. Refer to the