Chapter 9 Viewing Files and Reports

Viewing Waveforms

EM920 Power Quality and Revenue Meter

173

Viewing a Frequency Plot

Click on the

button to view a cycle-by-cycle frequency plot

for the sampled voltage waveforms.

Viewing a Spectrum Chart

Click on the

button to view a spectrum chart for the

selected waveform channel. PAS provides voltage, current,
active power and reactive power spectrum charts.

To change a channel, click on the window with the right
mouse button, select “Channels...”, check the channel you
want displayed, and then click OK.

Spectrum components are calculated over four cycles of the
waveform from the point where the left marker line is
located. If more than one view are open, PAS gives the
priority to the overlapped waveform view.

The order of the highest displayed harmonic component is
equal to the half sampling rate at which the waveforms are
sampled minus one.

PAS can also give you indication on whether harmonic levels
in the sampled waveforms exceed compliance limits defined
by the power quality standards or local regulations.