Configuring recorders, Configuring meter memory – SATEC EM920 Operation Manual User Manual

Page 105

Advertising
background image

Chapter 5 Configuring the EM920

Configuring Recorders

EM920 Power Quality and Revenue Meter

105

Configuring Recorders

The EM920 is provided with a 16-MByte onboard flash
memory for data, event and waveform recording.

The meter memory is fully configurable except of the files
that keep monthly and daily billing profiles and energy load
profile. They are pre-configured at the factory and may not
be changed by the user.

Two of the data log files are automatically configured in your
meter for recording EN51060 compliance statistics data and
harmonics survey data. You cannot change the file records
structure, but you can still change the amount of memory
allocated for these files.

The remaining memory can be freely partitioned. If you wish
to change the factory settings, follow the guidelines in the
next section.

Configuring Meter Memory

To view the present memory settings, select Memory/Log
from the Meter Setup menu, and then click on the Log
Memory tab.

The following table describes file options.

Option Range

Description

Type Wrap-around

Non-wrap

Wrap-around: recording continues over the oldest records.
Non-wrap: recording is stopped until the file is cleared.

Size

The memory size allocated to the file. It is set automatically
depending on the size of the records and the number of

records in the file.