CIP Information Appendix B
Discrete Input Point Object
Class Code 0x0008
The following class attributes are currently supported for the Discrete Input
Point Object:
Two instances of the Discrete Input Point Object are supported. All instances
contain the following attributes.
The following common services will be implemented for the Discrete Input Point
Object.
To obtain the status of an input point (ON or OFF), configure a CIP message as
shown below:
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
0xC7
2
2
Get
Max Instance
UINT
4
Attribute ID
Access Rule
Name
Data Type
Value
3
Get
Value
BOOL
0 = OFF, 1 = ON
5
FilterOffOn
0xC7
0 = No Delay
1000 = 1 ms
2000 = 2 ms
4000 = 4 ms
8000 = 8 ms
16000 = 16 ms
6
FilterOnOff
0xC7
0 = No Delay
1000 = 1 ms
2000 = 2 ms
4000 = 4 ms
8000 = 8 ms
16000 = 16 ms
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single