Ip address 888 – Rockwell Automation 56RF RFID System User Manual User Manual

Page 44

Advertising
background image

44

Rockwell Automation Publication 56RF-UM001A-EN-P - October 2011

Chapter 4

EtherNet/IP Addressing

Close and re-open the RSWho window. The older addresses are not available and
the new addresses (192.168.3.115 and 192.168.3.214) appear.

Note:

If DHCP is not disabled, the Bul. 56RF interface block will show two

requests in the DHCP Server at each power up.

In the picture below, power was cycled to the Bul. 56RF interface block at
7:45:16, 7:47:47, 7:49:06 and again at 10:56:00. Each time power was applied,
the Bul. 56RF interface block notified the BootP/DHCP server of its IP
Address. This indicates that DHCP has not been disabled. If DHCP is disabled,
the Bul. 56RF interface block would show nothing.

IP Address 888

Address 888 is used to reset the interface block to the factory defaults. Rotate the
address switches to 888 and cycle the power. The interface block clears out the
current assigned IP Address.

The MOD indicator blinks the following pattern: blinks red once, green once,
then solid red, then blinks green once, and final blinks continuous red about once
each second. The reset process takes about 10 seconds.

Advertising