Rockwell Automation 56RF RFID System User Manual User Manual

Page 58

Advertising
background image

58

Rockwell Automation Publication 56RF-UM001A-EN-P - October 2011

Chapter 7

RSLogix 5000 Controller Tags

• CRN

– The Configuration Revision Number is used internally with

RSLogix for configuration information. The user does not need to use this
tag.

• Pt00FaultMode

– The Pt00FaultMode is used in conjunction with

FaultValue to configure the state of output 0 when a communications fault
occurs. A value of 0 means that, in the case of a communications fault, the
value in FaultValue will be used (Off or On). A value of 1 means that the
last state will be held. By default this value is 0.

• Pt00FaultValue

– The Pt00FaultValue is used in conjunction with

FaultMode to configure the state of output 0 when a communications fault
occurs. A value of 0 is Off, and a value of 1 is On. By default the value is 0.

• Pt00FilterOffOn

– The Pt00FilterOffOn is used to determine the Off to

On delay time for input point 0 before the interface considers the input
point on or True. A value of 0 indicates there is no delay from an off
condition to an on condition; the only delay would be a hardware delay. A
value >0 would delay the input turning on by the configured value in
milliseconds. By default this value is 0.

• Pt00FilterOnOff

– The Pt00FilterOnOff is used to determine the On to

Off delay time for input point 0 before the interface considers the input
point off or False. A value of 0 indicates there is no delay from an on to off
condition; the only delay would be a hardware delay. A value >0 would
delay the input turning off by the configured value in milliseconds. By
default this value is 0.

• Pt00NoLoadEn

– The Pt00NoLoadEn is used to enable or disable No

Load diagnostic detection for output 0. A value of 1 means that No Load
diagnostic detection is enabled. A value of 0 means that No Load
diagnostic detection is disabled. By default this value is 0.

• Pt00OpenWireEn

– The Pt00OpenWireEn is used to enable or disable

the open wire detection for input point 0. A value of 1 means that open
wire detection is enabled. A value of 0 means that open wire detection is
disabled. By default this value is 1.

• Pt00OutputShortCircuitEn

– The Pt00OutputShortCircuitEn is used

to enable or disable the short circuit detection for output point 0. A value
of 1 means that short circuit detection is enabled. A value of 0 means that
short circuit detection is disabled. By default this value is 0.

• Pt00ProgMode

– The Pt00ProgMode is used in conjunction with

ProgValue to configure the state of output 0 when the controller is in
Program mode. A value of 0 means that the ProgValue (Off or On) will be
used when the controller is in Program mode. A value of 1 means that the
last state will be held. By default this value is 0.

• Pt00ProgValue

– The Pt00ProgValue is used in conjunction with

ProgMode to configure the state of output 0 when the controller is in
Program mode. A value of 0 is Off, and a value of 1 is On. By default this
value is 0.

• Pt00ShortCircuitEn

– The Pt00ShortCircuitEn is used to enable or

disable the short circuit detection for input point 0. A value of 1 means
that short circuit detection is enabled. A value of 0 means that short circuit
detection is disabled. By default this value is 0.