Figure 2 - Installation

Wiring

The EtherNet/IP Communications Auxiliary can accept all forms of DeviceNet
cable. However, DeviceNet shielded cable is recommended. The EtherNet/IP
Communications Auxiliary complies with the Open Device Vendors Association
(ODVA) DeviceNet compliance testing when the distance between end nodes is
100 m or less with 60 or fewer network drops.

Table 1 - Wire & Torque Specifications

Front View

37.44 mm

(1-1/2 in.)

37.44 mm

(1-1/2 in.)

Wire

Torque

1X
2X

24…12 AWG
24…16 AWG

5 lb.•in.

1X
2X

0.2…2.5 mm

2

0.25…1 mm

2

0.56 N•m

1X
2X

0.2…2.5 mm

2

0.2…1 mm

2

0.56 N•m