Chapter 1
Figure 2 - Installation
Wiring
The EtherNet/IP Communications Auxiliary can accept all forms of DeviceNet
cable. However, DeviceNet shielded cable is recommended. The EtherNet/IP
Communications Auxiliary complies with the Open Device Vendors Association
(ODVA) DeviceNet compliance testing when the distance between end nodes is
100 m or less with 60 or fewer network drops.
Table 1 - Wire & Torque Specifications
Front View
37.44 mm
(1-1/2 in.)
37.44 mm
(1-1/2 in.)
Wire
Torque
1X
2X
24…12 AWG
24…16 AWG
5 lb.•in.
1X
2X
0.2…2.5 mm
2
0.25…1 mm
2
0.56 N•m
1X
2X
0.2…2.5 mm
2
0.2…1 mm
2
0.56 N•m