Rockwell Automation Publication 193-UM014B-EN-P December 2011

73

Chapter

9

Device Parameters

Introduction

The EtherNet/IP Communications Auxiliary provides parameters to allow the
user to view the status and configure the DeviceNet scanner with RSNetWorx for
DeviceNet if the user does not want to use the internal web server of the
EtherNet/IP Communications Auxiliary. The 14 available parameters are listed
below.

Table 8 - Parameter List

Parameter Programming

Parameter Listing

The details for each of the 14 available parameters are listed below.

Table 9 - Parameter 1 — Scanner Status

1

Scanner Status

8

SL Entry Size

2

SL Entry 1 Status

9

Device Keys

3

SL Entry 2 Status

10

Scanlist Config

4

SL Entry 3 Status

11

ADR Record

5

SL Entry 4 Status

12

ADR Enable

6

SL Entry 5 Status

13

DNet IO RPI

7

SL Entry 6 Status

14

DNet IO Inhibit

IMPORTANT

Parameter setting changes to the EtherNet/IP Communications Auxiliary
take effect immediately even during a “running” status.

Description

Access Rule

Data Type

Units

Value

Min.

Max. Default

Provides the status of the

Devicenet scanner.

Get

WORD

0

16383

0

Bit

0

On Line

3

No Scanner Messages

6

Initializing

1

Illegal Scan List

4

Transmit Failure

7

Duplicate MAC Failure

2

No Network Messages

5

In Idle Mode

8

Bus Off