Page 62

Advertising
background image

62

Rockwell Automation Publication 193-UM014B-EN-P December 2011

Chapter 7

2.

Open the Controller Tags window.

3.

Select the Monitor Tags tab.

An array of input and output tags were generated for each of the six scanned
devices. To control the output relays for the scanned device, use the output tags;
to obtain diagnostic information from the scanned device, use the input tags.

The format of output data is shown in the table to follow.

Table 6 - Output Assembly — Instance 100

The format of the input data is shown in the table to follow.

Table 7 - Input Assembly — Instance 101

Byte Size

Contents

Scan List I/O Size Data to be delivered to the first scan list entry.
Scan List I/O Size Data to be delivered to the second scan list entry.
Scan List I/O Size Data to be delivered to the third scan list entry.
Scan List I/O Size Data to be delivered to the fourth scan list entry.
Scan List I/O Size Data to be delivered to the fifthscan list entry.
Scan List I/O Size Data to be delivered to the sixth scan list entry.

Byte Size

Contents

4 bytes

Logix Status Word

2 bytes

DeviceNet Scanner Status (Parameter 1) See

Table 9 on page 73

2 bytes

Scan List Entry 1 Status Word (Parameter 2) See

Table 10 on page 74

2 bytes

Scan List Entry 2 Status Word (Parameter 3) See

Table 11 on page 74

2 bytes

Scan List Entry 3 Status Word (Parameter 4) See

Table 12 on page 74

2 bytes

Scan List Entry 4 Status Word (Parameter 5) See

Table 13 on page 75

2 bytes

Scan List Entry 5 Status Word (Parameter 6) See

Table 14 on page 75

2 bytes

Scan List Entry 6 Status Word (Parameter 7) See

Table 15 on page 75

Scan List I/O Size Produced I/O data from the first scan list entry.
Scan List I/O Size Produced I/O data from the second scan list entry.
Scan List I/O Size Produced I/O data from the third scan list entry.