Rockwell Automation Publication 193-UM014B-EN-P December 2011

75

Chapter 9

Table 13 - Parameter 5 — SL Entry 4 Status

Table 14 - Parameter 6 — SL Entry 5 Status

Table 15 - Parameter 7 — SL Entry 6 Status

Description

Access Rule

Data Type

Units

Value

Min.

Max. Default

Provides the status of the

fourth scan list entry in the

DeviceNet scanner.

Get

WORD

0

2047

0

Bit

0

On Line

4

No Such Device

8

Device Went Idle

1

Connection Timeout

5

Fragment Error

9

Automatic Device

Replacement Error

2

Keying Mismatch

6

Slave Initialization Error

3

Wrong Data Size

7

I/O Data Overflow

10

Acknoledgement Timeout

Description

Access Rule

Data Type

Units

Value

Min.

Max. Default

Provides the status of the

fifth scan list entry in the

DeviceNet scanner.

Get

WORD

0

2047

0

Bit

0

On Line

4

No Such Device

8

Device Went Idle

1

Connection Timeout

5

Fragment Error

9

Automatic Device

Replacement Error

2

Keying Mismatch

6

Slave Initialization Error

3

Wrong Data Size

7

I/O Data Overflow

10

Acknoledgement Timeout

Description

Access Rule

Data Type

Units

Value

Min.

Max. Default

Provides the status of the
sixth scan list entry in the

DeviceNet scanner.

Get

WORD

0

2047

0

Bit

0

On Line

4

No Such Device

8

Device Went Idle

1

Connection Timeout

5

Fragment Error

9

Automatic Device

Replacement Error

2

Keying Mismatch

6

Slave Initialization Error

3

Wrong Data Size

7

I/O Data Overflow

10

Acknoledgement Timeout