Chapter 10

DeviceNet

Network Status

(NS)

None

The EtherNet/IP

Communications Auxiliary is

not receiving power.

Check the DeviceNet cable

connections and verify that

24V DC exists between the red

and black terminals.

Green, Red,

Not Illuminated

Flashing

(once)

Normal

This is a normal power-up

sequence.

Green

Flashing

The EtherNet/IP

Communications Auxiliary is

not configured to scan any

DeviceNet slave devices.

Check the DeviceNet scan list

for the correct scanner

configuration.

Green

Solid

Normal operating state and

the EtherNet/IP

Communications Auxiliary is

scanning DeviceNet slave

devices.

No action is required.

Red

Flashing

One or more DeviceNet

connections timed out.

Reset the EtherNet/IP

Communications Auxiliary.

Red

Solid

Diagnostics test failed on

power-up/reset. An internal

fault exists.

Cycle power to the unit. If the

fault still exists, replace the

unit.

Duplicate DeviceNet module

address exists. Two modules

cannot have the same address.

Change the MAC address to a

valid setting and reset the

device.

A fatal communication error

occurred.

Check DeviceNet media for

proper installation.

Module Status

None

The EtherNet/IP

Communications Auxiliary is

not receiving power.

Check the DeviceNet cable

connections and verify that

24V DC exists between the red

and black terminals.

Green, Red,

Not Illuminated

Flashing

(once)

Normal

This is a normal power-up

sequence.

Green

Flashing

The EtherNet/IP

Communications Auxiliary is

proper;y scanning DeviceNet

slave devices, but it is not

being scanned by the

EtherNet/IP master.

Check the Ethernet scan list

for the correct scanner

configuration.

Green

Solid

Normal operating state, the

EtherNet/IP Communications

Auxiliary is scanning

DeviceNet slave devices, and

is allocated to its master.

No action is required.

Red

Flashing

One or more DeviceNet or

EtherNet/IP connections timed

out.

Reset the EtherNet/IP

Communications Auxiliary.

The EtherNet/IP

Communications Auxiliary is

not configured to scan any

DeviceNet slave devices.

Check the DeviceNet scan list

for correct scanner

configuration.

Red

Solid

Diagnostics test failed on

power-up/reset.

Cycle power to the device. If

the fault still exists, replace

the device.

Link

Link (front)

Link (back)

None

The EtherNet/IP

Communications Auxiliary is

not properly connected to an

Ethernet network.

Check the Ethernet cabling to

make sure it is properly

installed.

Green

Flashing

The Ethernet network is

properly connected.

No action is required.

Green

Solid

Communications are occurring

on the Ethernet network.

No action is required.

Status LED

Color

State

Possible Cause

Corrective Action