Recoverable Error Mode

In this mode, the EtherNet/IP Communications Auxiliary MS LED flashes red.
The device will respond to messages that are specified in offline mode recovery
message protocol.

Unrecoverable Error Mode

In this mode, the EtherNet/IP Communications Auxiliary MS LED illuminates a
solid red. The device continues in this state as long as the device is powered.

Troubleshooting
Procedures

The following table identifies possible causes and corrective actions when
troubleshooting EtherNet/IP related failures using the status LEDs.

Table 23 - Troubleshooting Procedures

Error Type

Description

LED State

Recoverable

Duplicate IP address detected.

Flashing Red

A device is not present on the DeviceNet scan list.

Error Type

Description

LED State

Unecoverable Power-up initialization failure.

Solid Red

Data communication error.

Status LED

Color

State

Possible Cause

Corrective Action

EtherNet/IP

Network Status

(NS)

None

The EtherNet/IP

Communications Auxiliary is

not receiving power.

Check the DeviceNet cable

connections and verify that

24V DC exists between the red

and black terminals.

Green, Red,

Not Illuminated

Flashing

(once)

Normal

This is a normal power-up

sequence.

Green

Flashing

The EtherNet/IP

Communications Auxiliary is

online, but with no

connections established.

Check the EtherNet/IP master

and its scan list for correct

scanner configuraton.

Green

Solid

Normal operating state and

the EtherNet/IP

Communications Auxiliary is

allocated to a master.

No action is required.

Red

Flashing

One or more EtherNet/IP

connections timed out.

Reset the EtherNet/IP master

device.

Red

Solid

Diagnostics test failed on

power-up/reset. An internal

fault exists.

Cycle power to the unit. If the

fault still exists, replace the

unit.

Duplicate EtherNet/IP module

address exists. Two modules

cannot have the same address.

Change the IP address to a

valid setting and reset the

device.

A fatal communication error

occurred.

Check Ethernet media for

proper installation.