Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 103

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

Specifications A-11

Bus current draw, max.

115 mA at 5V dc
(0.575 W)

115 mA at 5V dc (0.575
W)

175 mA at 5V dc (0.88 W) 175 mA at 5V dc

0 mA at 24V dc

Heat dissipation, max.

2.9 W

1.61 W

2.9 W at 30 °C (86 °F)
2.1 W at 55 °C (131 °F)

3.4 W at 26.4 dc

Signal delay, max. –
resistive load

On delay: 1/2 cycle
Off delay: 1/2 cycle

On delay: 0.1 ms
Off delay: 1.0 ms

On delay: 0.1 ms
Off delay: 1.0 ms

On delay: 0.5 ms
Off delay: 4.0 ms

Off-state leakage, max.

2 mA at 132V,
2.5 mA at 265V

1.0 mA

1.0 mA

0.1 mA at 26.4V dc

On-state current, min.

10 mA

1.0 mA

1.0 mA

1.0 mA

On-state voltage drop,
max.

1.5V at 0.5 A

1.0V dc

1.0V dc

0.3V dc at 0.5 A

Continuous current per
point, max.

0.25 A at 55 °C (131 °F)
0.5 A at 30 °C (86 °F)

0.5 A at 55 °C (131 °F)
1.0 A at 30°C (86 °F)

0.5 A at 55°C (131 °F)
1.0 A at 30°C (86 °F)

0.5 A at 60 °C (140 °F)

Continuous current per
common, max.

1.0 A at 55 °C (131 °F)
2.0 A at 30 °C (86 °F)

4.0A at 55°C (131 °F)
8.0A at 30°C (86°F)

4.0 A at 55°C (131 °F)
8.0 A at 30°C (86 °F)

2.0 A at 60 °C (140 °F)

Continuous current per
module, max.

2.0 A at 55°C (131°F)
4.0 A at 30°C (86°F)

4.0 A at 55°C;
8.0 A at 30°C

4.0 A at 55°C (131 °F)
8.0 A at 30°C (86 °F)

4.0 A at 60 °C (140 °F)

Surge current, max.

5.0 A (Repeatability is
once every 2 seconds for
a duration of 25 ms.)

2.0A (Repeatability is
once every 2 seconds at
55 °C (131 °F), once every
second at 30 °C (86 °F)
for a duration of 10 ms.)

2.0A (Repeatability is
once every 2 seconds at
55 °C (131 °F), once every
second at 30 °C (86 °F)
for a duration of 10 ms.)

2.0 A (Repeatability is
once every 2 s at 60 °C
(140 °F) for 10 ms.)

Power supply distance
rating

6 (The module may not be more than 6 modules away from the power supply.)

Isolated groups

Group 1:
Outputs 0 to 3
Group 2:
Outputs 4 to 7

Group 1:
Outputs 0 to 7

Group 1:
Outputs 0 to 15

Group 1: Outputs 0…15

Group 2: Outputs 16…31
(internally connected to
common)

Output group to
backplane isolation

Verified by one of the
following dielectric tests:
1836V ac for 1 s or 2596V
dc for 1 s.

265V ac working voltage
(IEC Class 2 reinforced
insulation)

Verified by one of the following dielectric tests:
1200V ac for 1 s or 1697V dc for 1 s.

75V dc working voltage (IEC Class 2 reinforced
insulation)

Verified by one of the
following dielectric tests:
1200V ac for 2 s or 1697V
dc for 2 s.

75V dc working voltage
(IEC Class 2 reinforced
insulation)

Output group to output
group isolation

Verified by one of the
following dielectric tests:
1836V ac for 1 s or 2596V
dc for 1 s.

265V ac working voltage
(IEC Class 2 reinforced
insulation)

Not applicable

Verified by one of the
following dielectric tests:
1200V ac for 2 s or 1697V
dc for 2 s.

75V dc working voltage
(IEC Class 2 reinforced
insulation)

Table A.14 Output Specifications

Specification

1762-OA8

1762-OB8

1762-OB16

1762-OB32T