Recommended user-supplied components, Recommended user-supplied components -15 – Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 81

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

Communication Connections 4-15

1761-CBL-PM02 Series C (or equivalent) Cable Wiring Diagram

Recommended User-supplied Components

These components can be purchased from your local electronics supplier.

Cable

Length

Connections from

to AIC+ External

Power Supply
Required

(1)

Power
Selection
Switch
Setting

(1)

1761-CBL-AS03
1761-CBL-AS09

3m (9.8 ft)
9.5m (31.17 ft)

SLC 500 Fixed,
SLC 5/01, SLC 5/02, and SLC 5/03
processors

port 3

yes

external

PanelView 550 RJ45 port

port 3

yes

external

(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to cable.

Table 4.7 User Supplied Components

Component

Recommended Model

external power supply and chassis ground

power supply rated for 20.4 to 28.8V dc

NULL modem adapter

standard AT

straight 9-25 pin RS-232 cable

see table below for port information if
making own cables

Programming
Device

Controller

9-Pin D-Shell

8-Pin Mini Din

9

RI

24V

1

8

CTS

GND

2

7

RTS

RTS

3

6

DSR

RXD

4

5

GND

DCD

5

4

DTR

CTS

6

3

TXD

TXD

7

2

RXD

GND

8

1

DCD

Advertising
This manual is related to the following products: