Publication 1762-UM001G-EN-P - March 2011

Communication Connections 4-11

Single Cable Connection

When connecting a single cable to the DH-485 connector, use the following
diagram.

Multiple Cable Connection

When connecting multiple cables to the DH-485 connector, use the following
diagram.

Table 4.4 Connections using Belden #3106A Cable

For This Wire/Pair

Connect This Wire

To This Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue

Blue

Terminal 3 - (Common)

White/Orange

White with Orange Stripe

Terminal 4 - (Data B)

Orange with White Stripe

Terminal 5 - (Data A)

Table 4.5 Connections using Belden #9842 Cable

For This Wire/Pair

Connect This Wire

To This Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue/White

White with Blue Stripe

Cut back - no connection

(1)

(1) To prevent confusion when installing the communication cable, cut back the white with blue stripe wire

immediately after the insulation jacket is removed. This wire is not used by DH-485.

Blue with White Stripe

Terminal 3 - (Common)

White/Orange

White with Orange Stripe

Terminal 4 - (Data B)

Orange with White Stripe

Terminal 5 - (Data A)

Orange with White Stripes

White with Orange Stripes

Shrink Tubing Recommended

Blue (#3106A) or
Blue with White
Stripes (#9842)

Drain Wire

6 Termination

5 A
4 B
3 Common
2 Shield
1 Chassis Ground

to Next Device

to Previous Device