System Loading and Heat Dissipation F-3

Table F.3 Validating Systems Using 1762-L24AWA, 1762-L24BXB, 1762-L24AWAR or 1762-L24BXBR

Maximum Allowable Values

Calculated Values

Current:

Current (Subtotal 1 + Subtotal 2 from Table F.1 and Table F.2 on page F-2.):

400 mA at 5V dc

350 mA at 24V dc

0 mA + 260 mA = 260 mA at 5V dc

120 mA + 180 mA = 300 mA at 24V dc

System Loading:

System Loading:

10.4 Watts

= (260 mA x 5V) + (300 mA x 24 V)

= (1300 mW) + (7200 mW)

= 8500 mW

= 8.50 Watts

Table F.4 Validating Systems using 1762-L24BWA or 1762-L24BWAR

Maximum Allowable Values

Calculated Values

Current for Devices Connected to the +24V dc
Sensor Supply:

Sum of all sensor currents

250 mA at 24V dc

140 mA at 24V dc (example sensor value)

Current for MicroLogix Accessories and
Expansion I/O:

Current Values (Subtotal 1 from Table F.1 + Subtotal 2 from Table F.2):

400 mA at 5V dc

350 mA at 24V dc

0 mA + 260 mA = 260 mA at 5V dc

120 mA + 180 mA = 300 mA at 24V dc

System Loading:

System Loading:

12 Watts

= (140 mA x 24 V) + (260 mA x 5 V) + (300 mA x 24 V)

= (3360 mW) + (1300 mW) + (7200 mW)

= 11,860 mW

= 11.9 Watts