Publication 1762-UM001G-EN-P - March 2011

2-14 Install Your Controller

Mount the Controller

MicroLogix 1200 controllers are suitable for use in an industrial environment
when installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution degree
2

(1)

) and to circuits not exceeding Over Voltage Category II

(2)

(IEC

60664-1).

(3)

(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that

occasionally a temporary conductivity caused by condensation shall be expected.

(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient

voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.

(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)

designations.

ATTENTION

Do not remove the protective debris shield until after
the controller and all other equipment in the panel
near the controller are mounted and wiring is
complete. Once wiring is complete, remove
protective debris shield. Failure to remove shield
before operating can cause overheating.

ATTENTION

Electrostatic discharge can damage semiconductor
devices inside the controller. Do not touch the
connector pins or other sensitive areas.

TIP

For environments with greater vibration and shock
concerns, use the panel mounting method described
on page 2-16, rather than DIN rail mounting.

debris shield