Publication 1762-UM001G-EN-P - March 2011

Specifications A-7

Table A.10 Working Voltage (1762-L24BWA, 1762-L40BWA, 1762-L24BWAR, 1762-L40BWAR)

Attribute

1762-L24BWA, 1762-L40BWA, 1762-L24BWAR, 1762-L40BWAR

Power supply input to backplane isolation Verified by one of the following dielectric tests:1836V ac for 1 second or 2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation)

Input group to backplane isolation and
input group to input group isolation

Verified by one of the following dielectric tests: 1200V ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced insulation)

Output group to backplane isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or 2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation).

Output group to output group isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or 2596V dc for 1 second

265V ac Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)

Table A.11 Working Voltage (1762-L24BXB, 1762-L40BXB, 1762-L24BXBR, 1762-L40BXBR)

Attribute

1762-L24BXB, 1762-L40BXB, 1762-L24BXBR, 1762-L40BXBR

Input group to backplane isolation and
input group to input group isolation

Verified by one of the following dielectric tests: 1200V ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced insulation)

FET output group to backplane isolation Verified by one of the following dielectric tests: 1200V ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced insulation)

Relay output group to backplane
isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or 2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation).

Relay output group to relay output
group and FET output group isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or 2596V dc for 1 second

265V ac Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced
insulation)