A-24 Specifications

Table A.30 DC-Input/Relay-Output Combination Module - 1762-IQ80W6 Relay
Contact Ratings

Volts
(max.)

Continuous
Amps per
Point (Max.)

Amperes

(1)

(1) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of

the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.

Voltamperes

Make

Break

Make

Break

240V ac

2.5 A

7.5 A

0.75 A

1800VA

180VA

120V ac

15 A

1.5 A

125V dc

1.0 A

0.22 A

(2)

(2) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing

28VA by the applied dc voltage. For example, 28VA/48V dc = 0.58 A. For dc voltage applications less than 14 V,
the make/break rating for relay contacts cannot exceed 2 A.

28VA

(2)

24V dc

2.0 A

1.2 A

28VA

(2)

Table A.31 DC-Input/Relay-Output Combination Module - 1762-IQ80W6 General
Specifications

Specification

Value

Dimensions

90 mm (height) x 87 mm (depth) x 40.4 mm (width)
height including mounting tabs is 110 mm

3.54 in. (height) x 3.43 in. (depth) x 1.59 in. (width)
height including mounting tabs is 4.33 in.

Shipping weight, approx.
(with carton)

280 g (0.62 lbs.)

Bus current draw, max.

110 mA @ 5V dc
80 mA @ 24V dc

Heat dissipation

5.0 W @ 30V dc
4.4 W @ 26.4V dc
(The Watts per point, plus the minimum W, with all points
energized.)

Power supply distance
rating

6

Isolated group

Group 1 (input 0…3)
Group 2 (input 4…7)
Group 3 (output 0…5)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak,
2 hours per axis.
Relay Operation: 1.5 G

Shock

Operating: 30G panel mounted, 3 pulses per axis
Relay Operation: 7G
Non-Operating: 50G panel mounted, 3 pulses per axis
(40G DIN Rail mounted)