System Loading and Heat Dissipation F-5

Table F.7 Validating Systems using 1762-L24AWA, 1762-L24BXB, 1762-L24AWAR or 1762-L24BXBR

Maximum Allowable Values

Calculated Values

Current:

Current (Subtotal 1 from Table F.5 + Subtotal 2 from Table F.6.):

400 mA at 5V dc

350 mA at 24V dc

mA at 5V dc

mA at 24V dc

System Loading:

System Loading:

10.4 Watts

= (________ mA x 5V) + (________ mA x 24V)

= __________ mW + __________ mW

= __________ mW

= __________ W

Table F.8 Validating Systems using 1762-L24BWA or 1762-L24BWAR

Maximum Allowable Values

Calculated Values

Current for Devices Connected to the +24V dc Sensor
Supply:

Sum of all sensor currents

Include 1761-NET-AIC here rather than in Table F.5, if it is powered externally by
the sensor supply

250 mA at 24V dc

mA at 24V dc

Current for MicroLogix Accessories and Expansion I/O: Current (Subtotal 1 from Table F.5 + Subtotal 2 from Table F.6.)

400 mA at 5V dc

350 mA at 24V dc

mA at 5V dc

mA at 24V dc

System Loading:

System Loading:

12 Watts

= (________ mA x 24 V) + (________ mA x 5V) + (________ mA x 24 V)

= __________ mW + __________ mW + __________ mW

= __________ mW

= __________ W