Publication 1762-UM001G-EN-P - March 2011

Communication Connections 4-13

For additional information on connecting the AIC+, refer to the Advanced
Interface Converter (AIC+) User Manual, publication 1761-UM004.

Cable Selection Guide

Item

Description

1

Port 1 - DB-9 RS-232, DTE

2

Port 2 - mini-DIN 8 RS-232 DTE

3

Port 3 - RS-485 Phoenix plug

4

DC Power Source selector switch
(cable = port 2 power source,
external = external power source connected to item 5)

5

Terminals for external 24V dc power supply and chassis ground

1761-CBL-PM02

(2)

1761-CBL-AP00

(2)

Cable

Length

Connections from

to AIC+

External
Power Supply
Required

(1)

Power
Selection
Switch
Setting

(1)

1761-CBL-AP00

(2)

1761-CBL-PM02

(2)

45 cm (17.7 in)
2m (6.5 ft)

SLC 5/03 or SLC 5/04 processors, ch 0

port 2

yes

external

MicroLogix 1000, 1200, or 1500

port 1

yes

external

PanelView 550 through NULL modem
adapter

port 2

yes

external

DTAM Plus / DTAM Micro

port 2

yes

external

PC COM port

port 2

yes

external

(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to cable.

(2) Series C or higher cables are required.

1761-CBL-HM02

(1)

1761-CBL-AM00

(1)

Advertising
This manual is related to the following products: