Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 151

Advertising
background image

Publication 1762-UM001G-EN-P - March 2011

System Loading and Heat Dissipation F-9

1762-OX6I

110

110

1762-IQ8OW6

110

80

Total Modules (6 maximum):

Subtotal 2:

(1) Refer to your expansion I/O Installation Instructions for Current Requirements not listed in this table.

(2) Only applicable to Series B I/O modules.

Table F.14 Calculating the Current for Expansion I/O

Table F.15 Validating Systems using 1762-L40AWA, 1762-L40BXB, 1762-L40AWAR or 1762-L40BXBR

Maximum Allowable Values

Calculated Values

Current:

Current (Subtotal 1 from Table F.13 + Subtotal 2 from Table F.14.):

600 mA at 5V dc

500 mA at 24V dc

System Loading:

System Loading:

15 Watts

= (________ mA x 5V) + (________ mA x 24V)

= __________ mW + __________ mW

= __________ mW

= __________ W

Table F.16 Validating Systems using 1762-L40BWA or 1762-L40BWAR

Maximum Allowable Values

Calculated Values

Current for Devices Connected to the +24V dc Sensor
Supply:

Sum of all sensor currents

Include 1761-NET-AIC here rather than in Table F.13, if it is powered externally by
the sensor supply

400 mA at 24V dc

mA at 24V dc

Current for MicroLogix Accessories and Expansion I/O: Current (Subtotal 1 from Table F.13 + Subtotal 2 from page Table F.14.):

600 mA at 5V dc

500 mA at 24V dc

mA at 5 V dc

mA at 24V dc

System Loading:

System Loading:

16 Watts

= (________ mA x 24V) + (________ mA x 5V) + (________ mA x 24V)

= __________ mW + __________ mW + __________ mW

= __________ mW

= __________ W